· The system shall replace the existing primary electric heat source or be installed in a newly finished area of the home (e.g., bonus room, addition, sunroom).
· Defined as a minimum 15.2 SEER2 and 8.1 HSPF2 or higher all-electric heat pump with a variable speed compressor, excluding two-stage compressors.
· The system shall produce 100% of rated heating capacity without backup heat at 17 degrees Fahrenheit.
· Cooling capacity shall not exceed 125% of cooling load at design conditions.
· The system must be installed by a manufacturer-certified installer.
· QCN must provide Manual J 8th edition with project submission and upload in the Residential Hub.
· The system shall meet TVA EnergyRight General Rebate qualifications.